2005-07-13 00:00:00DENIED:
 1.PROVIDE MANUFACTURER'S SUBMITTAL
 DATA FOR THE GENERATOR & SUB-BASE FUEL
 TANK.
  
 2.PROVIDE DISTANCE BETWEEN THE
 GENERATOR & THE EXISTING BUILDING.PLAN
 SHEET E-1 INDICATES 4 FT.PLEASE SHOW
 DISTANCES TO OPENINGS, SHOW COMPLIANCE
 WITH 2001 FBC(M)501.3.
  
 3.PROVIDE DETAIL OF HOW THE
 GENERATOR/FUEL SUB-BASE WILL BE ANCHORED
 TO THE SLAB.
  