| Plan Review Notes For Permit 05060829 |
| Permit Number |
05060829 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-07-11 00:00:00 | 1. PLEASE PROVIDE DETAILS ON GENERATOR | | | AND SUB-BASE FUEL TANK. | | | | | | 2. WHAT LISTINGS ARE PRESENT FOR | | | THE FUEL TANK. | | | | | | 3. THE VICINITY MAP HAS NO SCALE | | | PROVIDED. PLEASE PROVIDE MINIMUM | | | DISTANCES TO ADJACENT PROPERTY LINES | | | IMPORTANT BUILDINGS, EXIT DOORS, ETC. | | | | | | 4. SINCE THE PROPOSED FUEL TANK IS | | | ABOVE GROUND, PLEASE PROVIDE ALL DETAILS | | | REGARDING LISTINGS, SPECIFICATIONS, | | | LABELING, ETC.OF THE FUEL TANK. | | | | | | 5. FUEL INSTALLATION TO COMPLY WITH | | | NFPA 30. | | | | | | 6. WHAT EQUIPMENT IS THE GENERATOR | | | EXPECTED TO SUPPLY EMERGENCY POWER FOR. | | | | | | MIKE CARSILLO, CHIEF FIRE PREVENTION | | | OFFICER | | | 835-2910 | | | | | | |
|