Plan Review Notes
Plan Review Notes For Permit 05060829
Permit Number 05060829
Review Stop E
Sequence Number 1
Notes
Date Text
2005-06-29 00:00:00************ UNSAT **************
  
 1)NOTE: PLEASE SUBMIT MANUFACTURES
 SPECS/CUT SHEETS FOR GENERATOR, ATS, AND
 FUEL TANK.
 PLEASE BE SURE ALL EQUIPMENT INDICATES A
 LISTING FROM A NRTL. PLEASE SEE ATS TO
 BE SERVICE ENTRANCE RATED.THIS IS NOTED
 ON PLANS, HOWEVER SPECS MUST INDICATE
 THIS.
 215.5,225.36
  
 2)NOTE: PLEASE SEE DUE TO SPECS FOR ATS,
 NOT BEING SUBMITTED AT THIS TIME,THE MCB
 INDICATED FOR ATS CAN NOT BE VERIFIED IF
 LOCATED ON THE OUTSIDE OF THE ATS WITH A
 MANUAL MEANS OF DISC?
 110.27, 225.31-36
  
 3)NOTE: PLEASE SEE 445.13 FOR MIN SIZING
 OF CONDUCTORS.
  
 4)NOTE: PLEASE SEE NO LOAD CALCULATIONS
 FOR LOADS TO BE SERVED BY GENERATOR WERE
 SUBMITTED. PLEASE SEE 702.5
 220
  
 5)NOTE: PLEASE SEE ZONING COMMENTS FOR
 SITE/SURVEY. THIS SHALL INDICATE FLOOD
 ZONE AND BFE. UNIT SHALL BE MOUNTED
 ABOVE BFE.
  
 PLEASE SEE ANY POSSIBLE COMMENTS FROM
 OTHER REVIEWER(S) WHICH MAY AFFECT
 ELECTRICAL PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
  
  