Plan Review Notes
Plan Review Notes For Permit 05060776
Permit Number 05060776
Review Stop P
Sequence Number 1
Notes
Date Text
2005-07-07 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
  
  
 1. SHT 1 ACCESSIBLE FIXTURE DETAILS.
 SHOW THE FOLLOWING:
 FOR WATER CLOSETS
 A. FLUSH CONTROLS 11-4.16.5
 FOR LAVS
 A. FAUCETS 11-4.19.5
 FOR BREAK ROOM SINK
 A. SINK DEPTH 11-4.24.4
 B. CLEAR FLOOR SPACE 11-4.24.5 SHALL
 HAVE FORWARD APPROACH, AND EXTEND A
 MAXIMUM OF 19" UNDERNEATH THE SINK.
 C. EXPOSED PIPES & SURFACES 11-4.24.6
 D. FAUCETS 11-4.24.7
 2. SHTS 1 & 2, SHOW THE TURNING AREA IN
 EACH TOILET ROOM PER SECTION 11-4.22.3.
 THE TURNING AREA SHALL BE UNOBSTRUCTED,
 AND THE WATER CLOSET SHALL NOT BE INSIDE
 THE AREA.
 3. SHT 7 SANT. RISER DIAGRAM FOR TENANT
 #2, FITTINGS SHALL BE INSTALLED TO GUIDE
 THE WASTE & SEWAGE IN THE DIRECTION OF
 FLOW. SECTION 706.3. FITTINGS FOR THE
 W/C'S ARE GUIDING AGAINST THE FLOW.
 4. SHT 7 WATER RISER DIAGRAM, WATER
 HEATERS SHALL INDICATE REQUIRED THERMAL
 EXPANSION CONTROL PER SECTION 607.3.2.
 5. AN RPZ BACKFLOW IS REQUIRED ON THE
 WATER SERVICE OF THE BUILDING. 608.13.2.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]
  
  
  
  
  
  
  
  