| Plan Review Notes For Permit 05060776 |
| Permit Number |
05060776 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-07-07 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 CHAPTER 1 | | | FBC-2001 CHAPTER 11 | | | | | | | | | 1. SHT 1 ACCESSIBLE FIXTURE DETAILS. | | | SHOW THE FOLLOWING: | | | FOR WATER CLOSETS | | | A. FLUSH CONTROLS 11-4.16.5 | | | FOR LAVS | | | A. FAUCETS 11-4.19.5 | | | FOR BREAK ROOM SINK | | | A. SINK DEPTH 11-4.24.4 | | | B. CLEAR FLOOR SPACE 11-4.24.5 SHALL | | | HAVE FORWARD APPROACH, AND EXTEND A | | | MAXIMUM OF 19" UNDERNEATH THE SINK. | | | C. EXPOSED PIPES & SURFACES 11-4.24.6 | | | D. FAUCETS 11-4.24.7 | | | 2. SHTS 1 & 2, SHOW THE TURNING AREA IN | | | EACH TOILET ROOM PER SECTION 11-4.22.3. | | | THE TURNING AREA SHALL BE UNOBSTRUCTED, | | | AND THE WATER CLOSET SHALL NOT BE INSIDE | | | THE AREA. | | | 3. SHT 7 SANT. RISER DIAGRAM FOR TENANT | | | #2, FITTINGS SHALL BE INSTALLED TO GUIDE | | | THE WASTE & SEWAGE IN THE DIRECTION OF | | | FLOW. SECTION 706.3. FITTINGS FOR THE | | | W/C'S ARE GUIDING AGAINST THE FLOW. | | | 4. SHT 7 WATER RISER DIAGRAM, WATER | | | HEATERS SHALL INDICATE REQUIRED THERMAL | | | EXPANSION CONTROL PER SECTION 607.3.2. | | | 5. AN RPZ BACKFLOW IS REQUIRED ON THE | | | WATER SERVICE OF THE BUILDING. 608.13.2. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] | | | | | | | | | | | | | | | | | | | | | | | | |
|