Plan Review Notes
Plan Review Notes For Permit 05060776
Permit Number 05060776
Review Stop E
Sequence Number 1
Notes
Date Text
2005-06-27 00:00:00** NOTES REDLINED ON PLANS **
  
 MISSING SIGN CIRCUITS FOR BOTH TENANTS
 PER 600.5
  
 SEE 210.8B3 FOR ALL RECEPTS IN KITCHEN.
 (2002 NEC )
  
 SEE 2 GRNDS ROODS REQUIRED. 250.50