| 2005-07-24 00:00:00 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | |
| | FBC FLORIDA BUILDING CODE 2001 |
| | FBC* CITY OF WEST PALM BEACH AMENDMENTS |
| | TO THE FBC2001 |
| | |
| | 1.)A NOTICE OF COMMENCEMENT MUST BE |
| | FILED WITH THE CLERK OF COURTS BEFORE A |
| | PERMIT CAN BE ISSUED. |
| | |
| | 2.)PROVIDE A SURVEY AND SITE PLAN. |
| | |
| | 3.)THE TITLE BLOCK IS REQUIRED TO |
| | INCLUDE THE FIRM LICENSE NUMBER (FOR |
| | ROBERT L BELL ARCHITECT PA) AND PRINTED |
| | NAME OF THE PERSON WHO HAS SEALED THE |
| | DOCUMENT, FAC61G1-16.003,004. |
| | |
| | 4.)A TYPE IV FOR THIS BUILDING IS |
| | DECLARED ON SHEET 1.THIS IS IN |
| | CONFLICT WITH DETAIL 1-3 WHICH SHOWS A |
| | METAL FRAME WALL WITH PLYWOOD SHEATHING |
| | AND DETAILS FOR THE PARAPET WALL WHICH |
| | ALSO SHOW PLYWOOD SHEATHING.NOTE THAT |
| | TYPE VI CONSTRUCTION IS NOT ALLOWED IN |
| | THE FIRE DISTRICT, FBC*F102.1. |
| | |
| | 5.)SHOW TURNING CLEARANCE FOR THE |
| | BATHROOMS, FBC11-4.22.3. |
| | |
| | 6.)THE ENERGY CALCS SUBMITTED APPEAR |
| | TO BE FOR THE TWO DIFFERENT TENANT |
| | SPACES, BUT BOTH HAVE 2800 AS THE SQUARE |
| | FOOTAGE.THIS IS THE TOTAL FOR THE |
| | ENTIRE BUILDING, NOT THE TENANT SPACES. |
| | CLARIFY. |
| | |
| | 8.)FBC1503.4.4, CONDENSATE LINES AND |
| | ROOF DOWNSPOUTS SHALL DISCHARGE AT LEAST |
| | 1 FOOT (305 MM) AWAY FROM THE STRUCTURE |
| | SIDEWALL, WHETHER BY UNDERGROUND PIPING, |
| | TAIL EXTENSIONS, OR SPLASH BLOCKS.NOTE |
| | THE 1? DIMENSION ON THE PLAN, SHEET 2. |
| | |
| | 9.)FLORIDA STATE OR LOCAL PRODUCT |
| | APPROVAL REQUIRED IN ADDITION TO THE |
| | FIXED GLASS NOA PROVIDED. |
| | |
| | 10.)IN ADDITION TO THE FIXED GLASS |
| | WINDOW, PROVIDE PRODUCT APPROVALS FOR |
| | THE FRENCH DOORS AND THE HOLLOW METAL |
| | DOOR.ANY PRODUCT APPROVALS NOT |
| | SUBMITTED AND REVIEWED PRIOR TO PERMIT |
| | ISSUANCE WILL REQUIRE SEPARATE PERMITS. |
| | |
| | 11.)SEE ATTACHED POLICY IN REGARDS TO |
| | IMPACT PROTECTION, ITEM #13.BE ADVISED |
| | THAT ALL GLAZING IS TO BE IMPACT UNLESS |
| | APPROVED BY THE BUILDING OFFICIAL. |
| | |
| | |