| Plan Review Notes For Permit 05060752 |
| Permit Number |
05060752 |
|
| Review Stop |
M |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2005-11-30 00:00:00 | ----------------PROVISO----------------- | | | 1) SLEEPING ROOM SHALL HAVE BALANCED | | | RETURN AIR PER FBC,M 601.4 | | | | | | 2) PLAN DOES NOT INDICATE A FIRE DAMPER | | | LOCATED IN A/C CLOSET AT SUPPLY PLENUM | | | CEILING PENETRACTION AS REQUIRED BY NOTE | | | 3 ON PLAN.PROVIDE FIRE DAMPER | | | MANUFACTURER'S INSTALLATION INSTRUCTIONS | | | ON-SITE FOR INSPECTION. | | | | | | RONALD J REGUEIRO | | | 561.805.6734 | | | [email protected] |
|