| 2005-10-20 00:00:00 | ********* UNSAT ************* |
| | |
| | PLEASE SEE SOME NOTES FROM PREVIOUS |
| | REVIEW AND SOME NEW NOTES DUE |
| | INFORMATION NOW SHOWN. |
| | |
| | |
| | 1)NOTE: PLEASE SEE LETTER FROM ARCHITECT |
| | PERTAINING TO SIGNATURE VERIFICATION. |
| | PLEASE SEE TITLE BLOCKS ON LTRS ARE |
| | STILL INDICATING "ENGINEER'S". |
| | PLEASE ALSO SEE THAT LETTER MUST BE |
| | CORRECTLY NOTORIZED UNDER FS 117.05. |
| | |
| | 2)NOTE: PLEASE SEE SERVICE SHOWN |
| | INDICATES AN EXISTING 60A SERVICE WITH |
| | 110A'S LOAD? |
| | PLEASE SEE PANEL SCHEDULE ALSO MENTIONS |
| | MIN SERVICE TO BE 125A'S , HOWEVER |
| | PANELS/RISER WAS NOT INCREASED TO SHOW |
| | AN UPGRADE IN THE ELECTRICAL SERVICE. |
| | PLEASE SUBMIT A NEW REVISED ELECTRICAL |
| | RISER DIAGRAM, PANEL, CONDUCTORS, ETC. |
| | PLEASE SEE 310.16,240.4, ETC. |
| | |
| | 3)NOTE: PLEASE SEE MISSING GFI RECEPT |
| | REQUIRED ON PENINSULAR. 210.52C3 |
| | |
| | 4)NOTE: PLEASE SEE MISSING REQUIRED |
| | DEDICATED BATH CIRCUIT PER |
| | 210.52D,210.11C3, MUST BE 20A AND #12. |
| | |
| | |
| | 5)NOTE: PLEASE SEE COPY OF FS |
| | 553.80(2)(B) WITH RESPECT TO DESIGN |
| | PROFESSIOAL AND REPEAT COMMENTS ON PLAN |
| | REVIEWS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |