| Plan Review Notes For Permit 05060752 |
| Permit Number |
05060752 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-06-20 00:00:00 | *********UNSAT ********* | | | | | | 1)NOTE: PLEASE INCLUDE ALL CIRCUTING ON | | | PLANS AND CORRELATE WITH A PANEL | | | SCHEDULE TO BE SUBMITTED. | | | PLEASE VERIFY IF PANEL IS NEW OR | | | EXSITNG. | | | PLEASE INCLUDE LOAD/FEEDER SIZE TO UNTI. | | | PLEASE INCLUDE ALL MIN CIRCUITING PER | | | 2002 NEC, 210.52D, 210.11C1-3, 210.12 | | | 210.52A,B,C , 210.52CC-5 ETC | | | | | | 2)NOTE: PLEASE CORRELATE TITLE BLOCK AS | | | SHOWN WITH FIRM # AND NAME LISTED WITH | | | STATE DBPR. STATE DOES NOT INCLUDE | | | ENGINEERS AS ARCH FIRM AND A SEPARATE | | | CA#MAY BE REQUIRED PER FS 471.023, FAC | | | 61G15-23.002 | | | | | | 3)NOTE: PLEASE SEE PLANS APPEAR TO BE | | | "SIGNED" WITH INITIALS? PLEASE SEE FS | | | 481.221, FAC 61G1-16PLEASE SEE IF THIS | | | IS INDEED "LEGAL SIGNATURE" , PLEASE | | | PROVIDE A SIGNED, SEALED NOTORIZED | | | LETTER FOR VERIFICATION. THIS WILL BE | | | PLACED IN SIGNATURE FILE FOR FUTURE | | | REFERENCE. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | CONSTUCTION SERVICES DEPT. | | | 561-805-6717 | | | [email protected] | | | | | | | | | |
|