Date Text
2005-06-20 00:00:00*********UNSAT *********
  
 1)NOTE: PLEASE INCLUDE ALL CIRCUTING ON
 PLANS AND CORRELATE WITH A PANEL
 SCHEDULE TO BE SUBMITTED.
 PLEASE VERIFY IF PANEL IS NEW OR
 EXSITNG.
 PLEASE INCLUDE LOAD/FEEDER SIZE TO UNTI.
 PLEASE INCLUDE ALL MIN CIRCUITING PER
 2002 NEC, 210.52D, 210.11C1-3, 210.12
 210.52A,B,C , 210.52CC-5 ETC
  
 2)NOTE: PLEASE CORRELATE TITLE BLOCK AS
 SHOWN WITH FIRM # AND NAME LISTED WITH
 STATE DBPR. STATE DOES NOT INCLUDE
 ENGINEERS AS ARCH FIRM AND A SEPARATE
 CA#MAY BE REQUIRED PER FS 471.023, FAC
 61G15-23.002
  
 3)NOTE: PLEASE SEE PLANS APPEAR TO BE
 "SIGNED" WITH INITIALS? PLEASE SEE FS
 481.221, FAC 61G1-16PLEASE SEE IF THIS
 IS INDEED "LEGAL SIGNATURE" , PLEASE
 PROVIDE A SIGNED, SEALED NOTORIZED
 LETTER FOR VERIFICATION. THIS WILL BE
 PLACED IN SIGNATURE FILE FOR FUTURE
 REFERENCE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  