Plan Review Notes For Permit 05060749
Permit Number 05060749
Review Stop G
Sequence Number 2
Notes
Date Text
2006-12-06 10:50:29PAUL SCHMITZ
 [email protected] FBC 2001PLUMBING
 CODE PLAN REVIEW FBC2001FUEL GAS
 CODEPLAN REVIEW
  
 DENIED
  
 REFERENCE: FBC-2001 FUEL GAS
  
 THE FOLLOWING INFORMATION IS REQUIRED
 FOR THE GAS PERMIT REVISION:
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS WITH PIPE SIZES,
 PER FBC-2004 FUEL GAS CODE.
 2. N/A
 3.N/A
 4. THE FBC-2001FUEL GAS CODE SECS. 401.8
 THRU 401.8 THRU TABLES 402.5.2 AND TAB 402(1) THRU
 402(34)
  
 5. N/A
  
 6. N/A
 .
 7. N/A
 8. N/A
  
 9. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
  
 SHOW THE LOCATION OF ALL GAS PSI REGULATORS WITH SOV
 AND UNION AT EA REGULATOR,
 AND MFG CUT SHEETS.
  
 QUESTIONS 561-805-6692PAUL SCHMITZ