| Plan Review Notes For Permit 05060746 |
| Permit Number |
05060746 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2005-07-07 00:00:00 | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | | REVIEW. | | | | | | COMMENTS FROM PREVIOUS REVIEW. | | | | | | 2} THERE MUST BE 2 APPLIANCE CIRCUITS ON | | | THE PANEL SCHEDULE PER 220.16. SHOW | | | SAME. | | | | | | 3} SHOW LOCATION OF THE CONDENSING UNIT | | | AND DISCONNECT PER 440.14. ALSO SERVICE | | | RECEPTACLE LOCATION PER 210.63. | | | | | | 4} PLEASE VERIFY THE DRYER IS 110 VOLT | | | AS INDICATED ON THE PANEL SCHEDULE. SEE | | | 220.18. | | | | | | 5} INDENTIFY THE REQUIRED ARC FAULT | | | BREAKERS IN THE PANEL PER 210.12. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 | | | | | | |
|