Plan Review Notes
Plan Review Notes For Permit 05060746
Permit Number 05060746
Review Stop E
Sequence Number 2
Notes
Date Text
2005-07-07 00:00:00 
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 COMMENTS FROM PREVIOUS REVIEW.
  
 2} THERE MUST BE 2 APPLIANCE CIRCUITS ON
 THE PANEL SCHEDULE PER 220.16. SHOW
 SAME.
  
 3} SHOW LOCATION OF THE CONDENSING UNIT
 AND DISCONNECT PER 440.14. ALSO SERVICE
 RECEPTACLE LOCATION PER 210.63.
  
 4} PLEASE VERIFY THE DRYER IS 110 VOLT
 AS INDICATED ON THE PANEL SCHEDULE. SEE
 220.18.
  
 5} INDENTIFY THE REQUIRED ARC FAULT
 BREAKERS IN THE PANEL PER 210.12.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026
  
  