Plan Review Notes
Plan Review Notes For Permit 05060746
Permit Number 05060746
Review Stop E
Sequence Number 1
Notes
Date Text
2005-06-27 00:00:00 
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} PLEASE INDICATE THE SERVICE EQUIPMENT
 LOCATION ON THE PLAN. METER, DISCONNECT
 AND PANEL(S). 215.5.
  
 2} THERE MUST BE 2 APPLIANCE CIRCUITS ON
 THE PANEL SCHEDULE PER 220.16.
  
 3} SHOW LOCATION OF THE CONDENSING UNIT
 AND DISCONNECT PER 440.14. ALSO SERVICE
 RECEPTACLE LOCATION PER 210.63.
  
 4} PLEASE VERIFY THE DRYER IS 110 VOLT
 AS INDICATED ON THE PANEL SCHEDULE. SEE
 220.18.
  
 5} INDENTIFY THE REQUIRED ARC FAULT
 BREAKERS IN THE PANEL PER 210.12.
  
 6} SMOKE DETECTORS ARE REQUIRED PER
 NFPA-72 8-1.4.1.6.2 AND 905.2.2 FBC.
 PLEASE LOCATE ON PLAN.
  
 7} THE KITCHEN COUNTERTOP RECEPTACLES
 MUST COMPLY WITH 210.52(C)(1) SPACING
 AND 210.8(A)(6), GFI.
  
 8} THE ARCHITECTS SEAL IS REQUIRED ON
 THE PLANS. SEE FS 481.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026
  
  
  