| Notes |
| Date |
Text |
| 2005-06-27 00:00:00 | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | | REVIEW. | | | | | | 1} PLEASE INDICATE THE SERVICE EQUIPMENT | | | LOCATION ON THE PLAN. METER, DISCONNECT | | | AND PANEL(S). 215.5. | | | | | | 2} THERE MUST BE 2 APPLIANCE CIRCUITS ON | | | THE PANEL SCHEDULE PER 220.16. | | | | | | 3} SHOW LOCATION OF THE CONDENSING UNIT | | | AND DISCONNECT PER 440.14. ALSO SERVICE | | | RECEPTACLE LOCATION PER 210.63. | | | | | | 4} PLEASE VERIFY THE DRYER IS 110 VOLT | | | AS INDICATED ON THE PANEL SCHEDULE. SEE | | | 220.18. | | | | | | 5} INDENTIFY THE REQUIRED ARC FAULT | | | BREAKERS IN THE PANEL PER 210.12. | | | | | | 6} SMOKE DETECTORS ARE REQUIRED PER | | | NFPA-72 8-1.4.1.6.2 AND 905.2.2 FBC. | | | PLEASE LOCATE ON PLAN. | | | | | | 7} THE KITCHEN COUNTERTOP RECEPTACLES | | | MUST COMPLY WITH 210.52(C)(1) SPACING | | | AND 210.8(A)(6), GFI. | | | | | | 8} THE ARCHITECTS SEAL IS REQUIRED ON | | | THE PLANS. SEE FS 481. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 | | | | | | | | | |
|