Plan Review Notes
Plan Review Notes For Permit 05060737
Permit Number 05060737
Review Stop E
Sequence Number 3
Notes
Date Text
2005-09-03 00:00:00************* UNSAT **************
  
  
 1)NOTE: PLEASE SEE ELECTRICAL
 PLANS/WRING DIAGRAM SUBMITTED SHOWS A
 NEW SERVICE BEING INSTALLED.
 ELECTRICAL SERVICE WOULD BE REQUIRED TO
 BE UNDER A SEPARATE PERMIT.
 PLEASE ONLY INDCATE ELECTRICLA IN SCOPE
 OF WORK FOR NEW POOL.
 IF ELECTRICAL PANELS SHOWN ARE EXISITNG,
 PLEASE SHOW AS EXISTING.
 PLEASE SEE THAT ELECTRICAL PLANS HAVE
 BEEN VOIDED.
  
 2)NOTE: PLEASE SEE MAIN PANEL INDICATES
 ENMT FEEDING SUB PANEL ?? PLEASE SEE
 USES NOT PERMITTED IN 362.12
  
 3)NOTE: PLEASE SEE SPECS FOR ELECTRIC
 HEAT PUMP ARE STILL BEING SUBMITTED AND
 ATTACHED TO PLANS, HOWEVER PLANS
 INDICATE A GAS HEATER??
 PLEASE ALSO SEE GAS SPECS SUBMITTED
 SEPARATELY.
  
 4)NOTE: PLEASE SEE CA# IS NOT VISABLE IN
 TITLE BLOCK AS REQUIRED UNDER FAC
 61G15-23.002, FS 471.023
 PLEASE KNOW THIS REQUIRED ON ALL SHEETS
 AND FOR ALL TRADES WHETHER OR NOT
 COMMENT IS MADE BY OTHER REVIEWER(S).
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  