| Plan Review Notes For Permit 05060737 |
| Permit Number |
05060737 |
|
| Review Stop |
E |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2005-09-03 00:00:00 | ************* UNSAT ************** | | | | | | | | | 1)NOTE: PLEASE SEE ELECTRICAL | | | PLANS/WRING DIAGRAM SUBMITTED SHOWS A | | | NEW SERVICE BEING INSTALLED. | | | ELECTRICAL SERVICE WOULD BE REQUIRED TO | | | BE UNDER A SEPARATE PERMIT. | | | PLEASE ONLY INDCATE ELECTRICLA IN SCOPE | | | OF WORK FOR NEW POOL. | | | IF ELECTRICAL PANELS SHOWN ARE EXISITNG, | | | PLEASE SHOW AS EXISTING. | | | PLEASE SEE THAT ELECTRICAL PLANS HAVE | | | BEEN VOIDED. | | | | | | 2)NOTE: PLEASE SEE MAIN PANEL INDICATES | | | ENMT FEEDING SUB PANEL ?? PLEASE SEE | | | USES NOT PERMITTED IN 362.12 | | | | | | 3)NOTE: PLEASE SEE SPECS FOR ELECTRIC | | | HEAT PUMP ARE STILL BEING SUBMITTED AND | | | ATTACHED TO PLANS, HOWEVER PLANS | | | INDICATE A GAS HEATER?? | | | PLEASE ALSO SEE GAS SPECS SUBMITTED | | | SEPARATELY. | | | | | | 4)NOTE: PLEASE SEE CA# IS NOT VISABLE IN | | | TITLE BLOCK AS REQUIRED UNDER FAC | | | 61G15-23.002, FS 471.023 | | | PLEASE KNOW THIS REQUIRED ON ALL SHEETS | | | AND FOR ALL TRADES WHETHER OR NOT | | | COMMENT IS MADE BY OTHER REVIEWER(S). | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|