| Plan Review Notes For Permit 05060733 |
| Permit Number |
05060733 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-06-24 00:00:00 | DENIED | | | REFERENCE: FBC-2001 424.2 SWIMMING POOLS | | | FBC-2001 CHAPTER 1 | | | FLORIDA ADMINISTRATIVE CODE | | | FLORIDA STATUTES | | | | | | 1. APPLICATION DESCRIPTION INDICATES A | | | POOL & SPA, BUT SWIMMING POOL PLAN DOES | | | NOT SHOW A SPA. PLEASE CLARIFY. SECTION | | | 104.2.1. - APPLICATION STATES "DESCRIBE | | | PROJECT IN DETAIL". | | | 2. PIPING SCHEMATIC DOES NOT REFLECT THE | | | POOL DATA & EQUIPMENT & CRITERIA. PIPING | | | SCHEMATIC SHOWS A CLEANER LINE, SPA MAIN | | | DRAINS, SPA INLETS, ROSETTES (2 LINES), | | | POOL HEATER NOT SHOWN ON DATA & | | | EQUIPMENT & CRITERIA. PLEASE CORRELATE | | | SCHEMATIC WITH CRITERIAL. SECTION | | | 104.2.1. | | | 3. ENGINEERS SHALL LEGIBLY INDICATE THE | | | CERTIFICATE OF AUTHORIZATION NUMBER OF | | | THE ENGINEERING BUSINESS ON EACH SHEET. | | | FAC 61G15-23.002(2) & FS 471.025. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|