| Plan Review Notes For Permit 05060730 |
| Permit Number |
05060730 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-07-09 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 CHAPTER 1 | | | | | | | | | 1. SUBMIT CALCULATIONS FOR MINIMUM | | | FACILITIES. INDICATE THE SQUARE FOOTAGE | | | OF THE EXISTING BUILDING, THE SQUARE | | | FOOTAGE OF EACH OCCUPANCY, AND THE | | | SQUARE FOOTAGE OF THE ADDITION. INDICATE | | | THE NUMBER OF FIXTURES REQUIRED PER | | | TABLES 1003.1 (BLDG) AND 403.1 (PLMG). | | | 2. SUBMIT CALCULATIONS FOR PRIMARY AND | | | SECONDARY ROOF DRAINS. SHOW SF OF NEW | | | ROOF AND SHOW 1/2 AREA OF ALL VERTICAL | | | WALLS INCLUDING PARAPETS ADDED TO THE | | | AREA OF THE ROOF IN THE CALCULATIONS. | | | 3. MORE INFORMATION REQUIRED FOR ROOF. | | | APPLICATION INDICATES 6,263SF ADDITION, | | | BUT ROOF DRAIN AREAS ONLY ADD UP TO | | | 2,500SF. PLEASE CLARIFY. SECTION | | | 104.2.1. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|