2005-07-01 00:00:00************ UNSAT **********
  
 1)NOTE: PLEASE CLARIFY/SHOW NEW OR
 EXISTING ROOFTOP GFI RECEPT FOR A/C
 RTU'S. 210.63,210.8
  
 2)NOTE: PLEASE SEE MISSING RECEPT FOR
 SHOW WINDOW ON WEST AND NORTH OF SHOW
 RM.
 210.62
  
 3)NOTE: PLEASE SEE MDP IS SHOWN BLANK
 AND NO NEW LOADS AND/OR EXISTING LOADS
 ARE SHOWN?
 PLEASE ALSO SEE ALL CONTINUOUS LOADS AND
 LARGEST MOTOR LOADS TO BE SHOWN @125%.
 215.3,230.42,220 ETC.
  
 PLEASE SEE ANY POSSIBLE COMMENTS FROM
 OTHER REVIEWER(S) WHICH MAY HAVE AN
 AFFECT ON ELECTRICAL PLANS.
  
 PLEASE BE SURE ALL OLD/VOIDED SHEETS ARE
 REMOVED FROM SETS AND ONLY NEW REVISED
 SHEETS ARE INSERTED INTO COMPLETE SETS
 FOR REVIEW AND STAMPING.
 PLEASE SEE ONE SET OF OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE ONLY.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  