| Plan Review Notes For Permit 05060730 |
| Permit Number |
05060730 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-07-01 00:00:00 | ************ UNSAT ********** | | | | | | 1)NOTE: PLEASE CLARIFY/SHOW NEW OR | | | EXISTING ROOFTOP GFI RECEPT FOR A/C | | | RTU'S. 210.63,210.8 | | | | | | 2)NOTE: PLEASE SEE MISSING RECEPT FOR | | | SHOW WINDOW ON WEST AND NORTH OF SHOW | | | RM. | | | 210.62 | | | | | | 3)NOTE: PLEASE SEE MDP IS SHOWN BLANK | | | AND NO NEW LOADS AND/OR EXISTING LOADS | | | ARE SHOWN? | | | PLEASE ALSO SEE ALL CONTINUOUS LOADS AND | | | LARGEST MOTOR LOADS TO BE SHOWN @125%. | | | 215.3,230.42,220 ETC. | | | | | | PLEASE SEE ANY POSSIBLE COMMENTS FROM | | | OTHER REVIEWER(S) WHICH MAY HAVE AN | | | AFFECT ON ELECTRICAL PLANS. | | | | | | PLEASE BE SURE ALL OLD/VOIDED SHEETS ARE | | | REMOVED FROM SETS AND ONLY NEW REVISED | | | SHEETS ARE INSERTED INTO COMPLETE SETS | | | FOR REVIEW AND STAMPING. | | | PLEASE SEE ONE SET OF OLD/VOIDED SHEETS | | | SHOULD BE SUBMITTED FOR REFERENCE ONLY. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | CONSTUCTION SERVICES DEPT. | | | 561-805-6717 | | | [email protected] | | | | | 2005-06-30 00:00:00 | IN ELEC FOR REVIEW. |
|