| 2006-04-17 00:00:00 | ******REVISION DENIED****** |
| | REFERENCE: FBC-2004 FUEL GAS, AND CITY |
| | OF WEST PALM BEACH, AMENDMENTS TO |
| | FBC-2004, CHAPTER 1, ADMINISTRATION: |
| | |
| | THE FOLLOWING INFORMATION IS REQUIRED |
| | FOR PLAN REVIEW FOR THE GAS REVISION: |
| | |
| | 1. PER CITY AMENDMENTS SECTION 106 |
| | CONSTRUCTION DOCUMENTS: 106.1 SUBMITTAL |
| | DOCUMENTS. ALL INFORMATION, DRAWINGS, |
| | SPECIFICATIONS, AND ACCOMPANYING DATA |
| | SHALL BEAR THE NAME AND SIGNITURE OF THE |
| | PERSON RESPONSIBLE FOR THE DESIGN. |
| | 2. PER FBC 2004 FUEL GAS, INDICATE ON |
| | THE REVISION THE TYPE OF PIPING MATERIAL |
| | BEING USED. |
| | 3. PLEASE CLARIFY DELIVERY PRESSURE, RE- |
| | VISION INDICATES 2.5 LB PSI. DELIVERY |
| | PRESSURE IS EITHER A 0.5 LB PSI OR A 2 |
| | LB PSI SYSTEM. CLEARLY INDICATE ON THE |
| | DRAWING THE DELIVERY PRESSURE. NOTE: IF |
| | SYSTEM IS BEING REVISED TO A 2 LB PSI |
| | SYSTEM SUBMIT MANUFACTURE SHEETS FOR 2LB |
| | PSI REGULATORS, AND INDICATE THEIR |
| | LOCATION ON THE DRAWING PER FBC-2004 |
| | FUEL GAS SEC. 402.2 |
| | 4. FUTURE GENERATOR INDICATED ON DRAWING |
| | NEEDS TO HAVE A SHUT OFF VALVE AND A |
| | HARD CAP (PRESSURE CAP) INDICATED ON |
| | DRAWING. |
| | |
| | END OF COMMENTS: |
| | |