Plan Review Notes
Plan Review Notes For Permit 05060715
Permit Number 05060715
Review Stop M
Sequence Number 1
Notes
Date Text
2005-08-09 00:00:00MECH. PLAN REVIEW:
  
 1. A/C PERMIT VALUE MUST BE INCREST TO
 REFLECT SCOPE OF WORK.
  
 2. UP DATE NOTICE OF COMMENCEMENT MUST
 BE SUBMITED.
  
 3. A/C PLAN MUST REFLECT R/A OUT OF
 HABITABLE ROOMS.2003 FBC/M 601.4
  
 4. A.H.U. REQUIRE SAFE PANS UNDER UNITS
 WITH DRAIN PAN PROTECTION. 2003 FBC/M
 307.2.3 AUX. DRAIN PAN.
  
 5. UTILITY ROOM REQUIRES COMBUSTION AIR
 FOR GAS DRYER. 2000 FBC/M CHAPTED #7
  
 6. PLEASE COMPLY WITH PROVISO M-1
 9/20/04 PATTY KRAUSS MECH. PLAN REVIEW.
  
 PAT RAFTER 561/805/6728 OR 805/6719
 PATTY KRAUSS
  
 PLEASE CALL IF THEAR ANY QUESTIONS.


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved