| Plan Review Notes For Permit 05060675 |
| Permit Number |
05060675 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2006-01-09 00:00:00 | ********* UNSAT ********** | | | | | | | | | 1)NOTE: PLEASE SEE PANEL "A" IS MISSING | | | LOAD FROM PANEL "B"AND "C". | | | PLEASE ALSO SEE LOADS ON PANEL "B" AND | | | "C". SOME ARE SHOWN WITH 83 KW, 96, KW | | | ETC. | | | PLEASE ADJUST LOADS AND CALCUALTIONS. | | | 220, 215.5 | | | | | | 2)NOTE: PLEASE SEE MISSING RECEPT PER | | | 210.52 | | | | | | | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE IN CONTACTING | | | THIS OFFICE. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|