| Plan Review Notes For Permit 05060663 |
| Permit Number |
05060663 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-07-25 00:00:00 | BUILDING REVIEW PROVISO: | | | 1- SHUTTERS UNDER A SEPARATE PERMIT. | | | 2- NEED WORST CASE SCENARIO ENERGY CALCS | | | 3- CLARIFY DOOR/WINDOW SCHEDULE. DON'T | | | MIX TOGETHER DOOR/WINDOW SYMBOLS. | | | 4- REVISE DETAIL 5/D1: CONNECTOR HTS20 | | | CAN'T SUPPORT BEAM. | | | 5- UPDATE HUS26 NAIL SIZE.SEE CATALOGUE | | | 6- REVISE CONNECTOR SPECIFIED AT ENTRY | | | PORCH TO MATCH DETAILS 5/D1 AND 6/D1 | | | 7- RE-SUBMIT PRODUCT APPROVAL FOR: | | | A)ROOF TILE, B)SINGLE HUNG WINDOWS, | | | C)FIXED WINDOWS. | | | 8- SHEET A-5 SHEAR VALUES NOTE: PROVIDE | | | HAND CALCULATIONS. WHY USING TIMBER | | | CONSTRUCTION MANUAL FOR TAPCON VALUES? |
|