| Plan Review Notes For Permit 05060659 |
| Permit Number |
05060659 |
|
| Review Stop |
B |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2005-09-22 00:00:00 | BUILDING SUBMITTAL CHECKLIST: | | | 1- ENERGY CALCS: ROBIN FROM KENCO COMM. | | | CALLED TO SAY THAT ENERGY CALCS WILL BE | | | CHANGED AGAIN FROM WORST CASE TO | | | SPECIFIC HOUSE ORIENTATION. SUBMIT | | | REVISED CALCS. | | | | | | 2- SEPARATE PERMIT FOR SHUTTERS IS NOT | | | DONE YET. | | | | | | 3- REVISE ROOF FRAMING PLAN AT ENTRY | | | PORCH AREA. CONCRETE BEAM DOESN'T EXTEND | | | TO THE FOYER AREA. ALSO, KNEEWALL IS NOT | | | CONCRETE EITHER. REVISE FRAMING PLANS | | | AND SPECIFY CORRESPONDING CONNECTORS. | | | SEC. 104.2.1.2 CITY AMENDMENTS TO FBC. | | | | | | 4- TRUSS ANCHOR SCHEDULE: REVISE NUMBER | | | OF NAILS SPECIFIED FOR HUS26. SEE 2005 | | | CATALOGUE. | | | | | | 5- PROVIDE 1 HR FIRE RATED DOOR AT | | | ATRIUM WITH SWING AS SHOWN ON PLANS. | | | | | | 6- WINDOW MULLION SIZE SPECIFIED FOR | | | FIXED WINDOWS AT GREAT ROOM DOESN'T | | | RESIST THE DESIGN PRESSURES. REVISE AS | | | REQUIRED. | | | | | | 7- PROVIDE PRODUCT APPROVAL FOR WINDOW | | | MULLION SPECIFIED ABOVE FOR FIXED | | | WINDOWS AT GREAT ROOM. | | | | | | ***NOTE: | | | REVISED DRAWINGS WILL BE SUBJECT TO | | | REVISION FEES. | | | | | | JULIO GOMEZ | | | BUILDING PLANS EXAMINER | | | (561)805-6712 |
|