| Plan Review Notes For Permit 05060659 |
| Permit Number |
05060659 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-07-19 00:00:00 | BUILDING REVIEW PROVISO: | | | 1- NEED WORST CASE SCENARIO ENERGY CALCS | | | 2- SHUTTERS UNDER A SEPARATE PERMIT. | | | 3- ROOF FRAMING PLAN: REVISE CONNECTOR | | | SPECIFIED AT FRONT PORCH TO MATCH | | | DETAILS 4/D1 AND 5/D1. | | | 4- REVISE NAIL SIZE FOR HUS26 CONNECTOR. | | | 5- SPECIFY SIZE AND ANHORS FOR MULLION | | | AT LARGE WINDOWS IN GREAT ROOM AREA. | | | 6- RE-SUBMIT PRODUCT APPROVAL FOR: | | | A) 1 HR FIRE RATED ATRIUM DOOR ASSEMBLY. | | | B) FIXED WINDOWS. | | | C) SINGLE HUNG WINDOWS. | | | D) ROOF TILE. | | | E) WINDOW MULLION SPECIFIED FOR LARGE | | | FIXED WINDOWS AT GREAT ROOM AREA. | | | 7- PROVIDE CLEAR DOOR/WINDOW SCHEDULES. | | | NO MIXING DOOR & WINDOW SYMBOLS. |
|