| Plan Review Notes For Permit 05060623 |
| Permit Number |
05060623 |
|
| Review Stop |
M |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2005-09-16 00:00:00 | *** DENIDE *** | | | 1) RETURN TRANSFER DUCTS NEED TO BE | | | 1 1/2 TIMES LARGER THAN THE SUPPLY | | | AIR DUCTS. 2001 FBC/M 601.4 . | | | EXP. 7" SUPPLY AIR DUCT REQUIRES A 9" | | | RETURN AIR TRANSFER DUCT WITH A 1" | | | UNDERCUT DOOR, 8" SUPPLY AIR DUCT | | | REQUIRES A 10" RETURN AIR TRANSFER DUCT | | | WITH A 1" UNDERCUT DOOR. | | | IF YOU HAVE ANY QUESTIONS PLEASE CALL | | | TOM GORDON 805-6729 OR PATTY KRAUSS | | | 805-6719. |
|