| 2005-06-22 00:00:00 | | | | PLEASE INDICATE THE RATING AND OCP OF | | | THE DISCONNECT AND SUB-PANEL FOR THE | | | GENERATOR. | | | | | | SHOW THE LOCATION OF ALL EQUIPMENT ON A | | | SITE PLAN. | | | | | | INDICATE THE PRIME MOVER IN THE SPEC OR | | | ON THE DRAWING. | | | | | | THE FEEDERS ARE # 6 FROM A 100AMP | | | GENERATOR. PLEASE SEE 445.13, | | | 310.15(B)(6) FOR CORRECT SIZING. | | | | | | CALL WITH ANY QUESTIONS. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 |
|