| 2005-08-16 00:00:00 | | | | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | | REVIEW. | | | | | | 1} PLEASE INDICATE WHICH FLOOD ZONE THIS | | | PROJECT IS IN. PROVIDE A FLOOD ELEVATION | | | CERTIFICATE. | | | | | | 2} THE INFORMATION SUBMITTED FOR THE | | | TRANSFER SWITCH DOES NOT INDICATE IT IS | | | SERVICE RATED PER 225.36, . PLEASE | | | INDICATE THAT IT IS PER SPEC'S OR | | | INDICATE COMPLIANCE WITH THAT ARTICLE. | | | | | | 3} THE PLANS MUST BEAR THE SIGNATURE AND | | | PRINTED NAME OF THE PERSON RESPONSIBLE. | | | | | | 4} PLEASE ATTACH THE ORIGINAL PERMIT | | | APPLICATION WHEN RESUBMITTING. CURRENTLY | | | ONLY TWO HALF COPIES ARE IN THE PACKAGE. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] |
|