| Notes |
| Date |
Text |
| 2005-07-20 00:00:00 | DENIED: | | | 1.PROVIDE MANUFACTURER SUBMITTAL DATA | | | FOR THE DIESEL GENERATOR. | | | | | | 2.PROVIDE SITE PLAN OR SURVEY, | | | INDICATE DISTANCES FROM THE PROPERTY | | | LINES, AND ADJACENT BUILDINGS. | | | | | | 3.INDICATE DISTANCES FROM DOORS, | | | WINDOWS AND FRESH AIR INTAKES.SHOW | | | COMPLIANCE WITH 2001 FBC(M)401.5 & | | | 501.3. | | | | | | 4.PROVIDE DETAIL FOR ANCHORING OF THE | | | GENERATOR IN ACCORDANCE WITH 2001 FBC | | | 1606.1.3. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561)805-6719. |
|