2005-07-20 00:00:00DENIED:
 1.PROVIDE MANUFACTURER SUBMITTAL DATA
 FOR THE DIESEL GENERATOR.
  
 2.PROVIDE SITE PLAN OR SURVEY,
 INDICATE DISTANCES FROM THE PROPERTY
 LINES, AND ADJACENT BUILDINGS.
  
 3.INDICATE DISTANCES FROM DOORS,
 WINDOWS AND FRESH AIR INTAKES.SHOW
 COMPLIANCE WITH 2001 FBC(M)401.5 &
 501.3.
  
 4.PROVIDE DETAIL FOR ANCHORING OF THE
 GENERATOR IN ACCORDANCE WITH 2001 FBC
 1606.1.3.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.