Plan Review Notes
Plan Review Notes For Permit 05060589
Permit Number 05060589
Review Stop E
Sequence Number 1
Notes
Date Text
2005-06-16 00:00:00 
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} IT APPEARS THAT LINE AND LOAD FOR THE
 DISCONNECTS ARE IN THE SAME GUTTER. SHOW
 SEPARATION PER 230.7.
  
 2} SHOW LOCATION OF DISCONNECTING MEANS
 FOR GENERATOR FEEDERS PER 225.31, 32,
 36.
  
 3} SUBMIT MANUFACTURERS SPECS FOR THE
 GENERATOR AND TRANSFER SWITCH.
  
 4} THE PLANS INDICATE THE FEEDERS FROM
 THE GENERATOR ARE #4/0(CU?) AND THE
 GENERATOR APPEARS TO HAVE A 250 AMP OCP.
 SEE 445.13 FOR 115% AND 310.16 FOR
 ALLOWABLE AMPACITIES.
  
 5} PLEASE FURNISH CALCULATIONS FOR THE
 LOADS SELECTED TO BE SUPPLIED ON
 EMERGENCY POWER.
  
 6} THE COST OF ALL EQUIPMENT BEING
 INSTALLED MUST BE INCLUDED ON THE
 APPLICATIION, EVEN THOUGH OWNER
 SUPPLIED. 104.2.1 CWPB AMMENDMENTS.
  
 7} PLEASE INDICATE WHICH FLOOD ZONE THIS
 PROJECT IS IN.
  