| Plan Review Notes For Permit 05060589 |
| Permit Number |
05060589 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-06-16 00:00:00 | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | | REVIEW. | | | | | | 1} IT APPEARS THAT LINE AND LOAD FOR THE | | | DISCONNECTS ARE IN THE SAME GUTTER. SHOW | | | SEPARATION PER 230.7. | | | | | | 2} SHOW LOCATION OF DISCONNECTING MEANS | | | FOR GENERATOR FEEDERS PER 225.31, 32, | | | 36. | | | | | | 3} SUBMIT MANUFACTURERS SPECS FOR THE | | | GENERATOR AND TRANSFER SWITCH. | | | | | | 4} THE PLANS INDICATE THE FEEDERS FROM | | | THE GENERATOR ARE #4/0(CU?) AND THE | | | GENERATOR APPEARS TO HAVE A 250 AMP OCP. | | | SEE 445.13 FOR 115% AND 310.16 FOR | | | ALLOWABLE AMPACITIES. | | | | | | 5} PLEASE FURNISH CALCULATIONS FOR THE | | | LOADS SELECTED TO BE SUPPLIED ON | | | EMERGENCY POWER. | | | | | | 6} THE COST OF ALL EQUIPMENT BEING | | | INSTALLED MUST BE INCLUDED ON THE | | | APPLICATIION, EVEN THOUGH OWNER | | | SUPPLIED. 104.2.1 CWPB AMMENDMENTS. | | | | | | 7} PLEASE INDICATE WHICH FLOOD ZONE THIS | | | PROJECT IS IN. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 |
|