| Plan Review Notes For Permit 05060582 |
| Permit Number |
05060582 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2005-08-09 00:00:00 | ** UNSAT ** | | | | | | 1)NOTE; PLEASE SEE MISSING FPL METERING | | | DEVICE / METER CAN AT SERVICE LOCATION | | | AT TRANSFORMER. | | | PLEASE SEE SERVICE LOCATION AT | | | TRANSFORMER WILL BE REQUIRED TO CONTAIN | | | GROUDING ELECTRODE SYSTEM. | | | 250.50,250.24, 250.66. | | | PLEASE SEE SECONDARY LOCATION AT | | | TRAILERS WILL BE THE "DETACHED" | | | STRUCTURE. PLEASE VERIFY IF CWP PIPING | | | FOR TAILERS IS METAL? IF SO, CWP SHALL | | | BE A PART OF THE GROUNDING ELECTRODE | | | SYSTEM. 250.50 | | | | | | 2)NOTE: PLEASE VERIFY CONDUCTORS IN | | | RISER AND GUTTER. SHOW CONDUCTORS TO | | | SECONDARY MAINS AT GUTTER/ SERVICE RACK | | | LOCATION. CONDUCTORS IN RISER AT | | | TRANSFORMER LOCATION. | | | | | | PLEASE CALL, IF THERE ARE ANY QUESTIONS. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|