| 2005-08-18 00:00:00 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | [email protected] | | | | | | 1.)THE TOTAL RISE SHOWN ON BSP1 IS 36" | | | WITH FIVE RISERS, EACH INDIVIDUAL RISER | | | WOULD BE 7.2" WHICH EXCEEDS THE 7" | | | MAXIMUM FBC1007.3.1. THIS IS IN CONFLICT | | | WITH D-SP1 WHICH SHOWS 7" RISERS. | | | | | | 2.)THE HANDRAIL FOR THE STAIRS IS TO | | | BE ROUNDED OR RETURNED SMOOTHLY TO THE | | | FLOOR, FBC11-4.9.4(6).SEE FIGURE 11-19 | | | FOR AN EXAMPLE. | | | | | | 3.)FROM PREVIOUS LIST, SECTION B-SP1 | | | SHOWS ONE RAIL, D-SP1 (PLAN) APPEARS TO | | | SHOW TWO (GUARDRAIL AND HANDRAIL). | | | PLEASE CLARIFY WITH CODE COMPLIANT | | | DETAILS. TO FURTHER CLARIFY THE PREVIOUS | | | COMMENT, PLEASE PROVIDE A DETAIL FOR THE | | | GUARDRAIL IN COMPLIANCE WITH FBC1015. | | | THE PLAN APPEARS TO SHOW ONE BUT NO | | | DETAIL IS PROVIDED. | | | | | | 4.)A GUARDRAIL IS REQUIRED AT THE | | | RAMP AND DECK FBC1015.PLEASE PROVIDE | | | DETAILS. |
|