Plan Review Notes
Plan Review Notes For Permit 05060582
Permit Number 05060582
Review Stop E
Sequence Number 1
Notes
Date Text
2005-06-14 00:00:00*********** UNSAT ***********
  
 1)NOTE: PLEASE SUBMIT A COMPLETE
 ELECTRICAL RISER DIAGRAM SHOWING ALL
 DISCONNECTS, SEC'S, FEEDERS, CONDUIT(S),
 GROUNDING ELECTRODE SYSTEM, GROUNDING AT
 TRIALERS ETC.
 215.5,310.16,240.4,250,,,
  
 2)NOTE:PLEASE SUBMIT LOAD CALCULATIONS
 FOR TEMP SERVICE SERVING NEW TRAILERS.
 220/215.5
  
 PLEASE SEE ANY REVIEW COMMENTS FROM
 OTHER TRADES WHICH MAY AFFECT ELECTRICAL
 PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  