Plan Review Notes
Plan Review Notes For Permit 05060582
Permit Number 05060582
Review Stop B
Sequence Number 1
Notes
Date Text
2005-06-30 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)IT APPEARS THAT THE RISE OF THE
 STAIRS IS 7" (D-SP1); PLEASE PROVIDE THE
 RUN DIMENSION IN COMPLIANCE WITH
 FBC1007.3.1.
  
 2.)A-SP1, SPECIFY JOIST HANGER AND
 STRAP.
  
 3.)PLEASE PROVIDE A DETAIL FOR THE
 HANDRAILS IN COMPLIANCE WITH FBC11-4.26,
 FBC1007.5.
  
 4.)THE STAIR HANDRAILS ARE TO COMPLY
 WITH FBC
  
 4.)IF RAMPS CHANGE DIRECTIONS AT
 LANDINGS, THE MINIMUM LANDING SIZE SHALL
 BE 60 INCHES BY 60 INCHES FBC11-4.8.4.
  
 5.)SHOW THE 60" CLEAR AT THE TOP
 LANDING OF THE RAMP FBC11-4.8.4(2).
  
 6.)THE RAMP HANDRAILS ARE TO COMPLY
 WITH FBC11-4.8.5(2).
  
 7.)SECTION B-SP1 SHOWS ONE RAIL, D-SP1
 (PLAN) APPEARS TO SHOW TWO (GUARDRAIL
 AND HANDRAIL).PLEASE CLARIFY WITH CODE
 COMPLIANT DETAILS.SECTION B-SP1 DOES
 NOT SHOW A HANDRAIL AT THE REQUIRED
 HEIGHT FBC1007.5.
  
 8.)EXTENSIONS AT THE TOP AND BOTTOM OF
 THE STAIRS TO COMPLY WITH
 FBC11-4.9.4(2), FBC11 FIGURE 19.
  
 8.)SHOW THE ACCESSIBLE ROUTE TO THE
 RAMP AND ACCESSIBLE STAIR.A SIDEWALK
 IS SHOWN LEADING TO ONE STAIR BUT NOT
 SHOWN FOR THE RAMP/STAIR.