| Plan Review Notes For Permit 05060525 |
| Permit Number |
05060525 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-06-25 00:00:00 | BUILDING & PLUMBING PLAN REVIEW: DENIED | | | (1) FBC 2001 SEC 424.2.13.2 JOINTS AND | | | CONNECTIONS, FBC PLBG SEC 605.21, PURPLE | | | PRIMER REQUIRED ON PVC PIPING.( ADD TO | | | NOTES) | | | (2) SEC 424.2.14.1 SWIMMING POOL WATER | | | HEATERS SHALL BEAR THE LABEL OF A RECOG | | | NIZED TESTING AGENCY. MANFACTURE SHEETS | | | REQUIRED. (SUBMTITAL) | | | (3) SEC 424.2.14.2 WATER RETENTION, | | | PROVIDE A POSITIVE MEANS OF RETAINING | | | WATER IN THE HEATER WHEN PUMP IS SHUT | | | OFF.( MANFACTURE CUT SHEETS SUBMITTAL) | | | END OF COMMENTS QUESTIONS, | | | CONTACT PAUL SCXHMITZ 561-805-6692 |
|