Plan Review Notes
Plan Review Notes For Permit 05060524
Permit Number 05060524
Review Stop M
Sequence Number 1
Notes
Date Text
2005-06-27 00:00:00DENIED:
 PERMIT APPLICATION INDICATES THE VALUE
 OF WORK FOR "LABOR ONLY".HOMEOWNER TO
 SUPPLY GENERATOR.PER THE CITY
 AMENDMENTS 104.6.5, VALUATION SHALL
 INCLUDE COST FOR ALL EQUIPMENT, LABOR,
 OVERHEAD, AND PROFIT, EXCLUDING ONLY
 LAND VALUE.PLEASE ADJUST VALUE OF
 PERMIT ACCORDINGLY.
  
 PLAN INDICATES GENERATOR TO BE 12" FROM
 THE BUILDING STRUCTURE.PLEASE PROVIDE
 MANUFACTURER'S INSTALLATION INSTRUCTIONS
 FOR CLEARANCES.PLEASE NOTE, PER 2001
 FBC(M)804.3.5 #3 WHERE THE VENT
 TERMINATION IS LOCATED BELOW AN SDJACENT
 ROOF STRUCTURE, THER TERMINATION POINT
 SHALL BE LOCATED AT LEAST 3 FEET FROM
 THE STRUCTURE.
  
 ADDITIONAL PERMIT REQUIRED FOR LP GAS.
 PROVIDE PLAN INDICATE THE LOCATION &
 REQUIRED CLEARANCES FOR THE LP TANK IN
 ACCORDANCE WITH NFPA 58.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.