Plan Review Notes
Plan Review Notes For Permit 05060519
Permit Number 05060519
Review Stop B
Sequence Number 1
Notes
Date Text
2005-06-08 00:00:00DENIED
  
 1) THE PRODUCT APPROVAL SUBMITTED FOR
 THE MODIFIED BITUMEN SYSTEM HAS A
 MAXIMUM DESIGN PRESSURE OF -45 PSF WITH
 LIMITATION #9 WHICH DOES NOT ALLOW FOR
 ENHANCED FASTENER SPACING TO INCREASE
 DESIGN PRESSURE. THE PRESSURE AT CORNERS
 (ZONE 3) IS -89PSF.
  
 2) SPECIFY THE APPROVED ASSEMBLY THAT
 WILL BE INSTALLED. SEVERAL ARE IN THE
 NOA SUBMITTED. SOME ARE FOR INSULATED
 WOOD DECKS AND SOME ARE NON-INSULATED
 WOOD DECKS.
  
 CALL IF YOU HAVE QUESTIONS:
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714