| Plan Review Notes For Permit 05060508 |
| Permit Number |
05060508 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-06-08 00:00:00 | DENIED | | | | | | 1) SPECIFY THE MEAN ROOF HEIGHT OF THE | | | STRUCTURE ON THE APPLICATION. | | | | | | 2) THE DESIGN PRESSURES FOR THE APPROVED | | | SYSTEMS THAT WERE SUBMITED WILL NOT MEET | | | THE REQUIRED PRESSURES. ON A BUILDING UP | | | TO 30 FEET IN HEIGHT WITH A BASIC WIND | | | SPEED OF 140 MPH, THE REQUIRED DESIGN | | | PRESSURE FOR A FLAT ROOF IN ZONE 3 IS | | | -89 PSF. SEE FBC TABLE 1606.2B. | | | | | | IF YOU HAVE QUESTIONS CALL: | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 |
|