| Plan Review Notes For Permit 05060474 |
| Permit Number |
05060474 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-07-18 00:00:00 | BUILDING REVIEW PROVISO: | | | | | | 1- REVISE ENERGY CALCULATIONS FOR WORST | | | CASE SCENARIO FOR THIS MODEL. | | | 2- SHUTTERS UNDER A SEPARATE PERMIT. | | | 3- ROOF FRAMING PLAN: REVISE CONNECTOR | | | SPECIFIED AT FRONT PORCH. SEE DETAILS 4 | | | AND 5 OF SHEET D-1. | | | 4- TRUSS ANCHOR SCHEDULE: REVISE NAIL | | | SIZE FOR HUS26. SEE CATALOGUE. | | | 5- SPECIFY SIZE AND ANCHORS FOR LARGE | | | FIXED WINDOW AT GREAT ROOM. SEC. | | | 104.2.1.2 CITY AMENDMENTS TO FBC 2001. | | | 6- PROVIDE FLORIDA OR LOCAL PRODUCT | | | APPROVAL FOR: | | | A) 1 HR FIRE RATED DOOR AT ATRIUM. | | | B) FIXED WINDOWS. | | | C) SINGLE HUNG WINDOWS. | | | D) ROOF TILE. | | | E) WINDOW MULLION AT GREAT ROOM WINDOWS. | | | 7- CLARIFY WINDOW DOOR SCHEDULES | | | ICLUDING SIMBOLS USED ON PLAN. |
|