| Plan Review Notes For Permit 05060465 |
| Permit Number |
05060465 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2006-02-03 00:00:00 | ********* UNSAT ********* | | | | | | 1)NOTE: PLEASE SEE OCP HAS NOW BEEN | | | INCREASED FOR PANEL "B" TO 125A'S, | | | HOWEVER PLEASE SEE RISER HAS NOT | | | INCREASED PANEL ORFEEDERS AND PANEL | | | SCHEDULE ALSO SHOWS 100A. | | | PLEASE CORRELATE , UPGRADE PANEL, | | | FEEDERS ETC. | | | | | | 240.4,310.15B6, 215.5 ETC. | | | | | | | | | 2)NOTE: PLEASE SEE MIN GRND ROD 8' PER | | | 250.52A5 | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE IN CONTACTING | | | THIS OFFICE. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|