| Plan Review Notes For Permit 05060463 |
| Permit Number |
05060463 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-07-01 00:00:00 | BUILDING REVIEW PROVISO: | | | 1- PROVIDE THE REVISED ENERGY | | | CALCULATIONS FOR WORST CASE SCENARIO. | | | 2- SHUTTERS UNDER A SEPARATE PERMIT. | | | 3- ROOF FRAMING PLAN: REVISE CONNECTOR | | | SPECIFIED AT FRONT PORCH MASONRY BEAMS. | | | NEED MASONRY CONNECTOR. SEE DETAILS 4/D1 | | | AND 5/D1 AND REVISE AS REQUIRED. | | | 4- TRUSS ANCHOR SCHEDULE: REVISE NAIL | | | SIZE FOR HUS26. SEE CATALOGUE. | | | 5- PROVIDE PRODUCT APPROVAL FOR: | | | A) 1 HR FIRE RATED DOOR & EGRESS | | | ASSEMBLY. | | | B) FIXED WINDOWS NEED FLORIDA PRODUCT | | | APPROVAL COVER PAGE. | | | C) SINGLE HUNG WINDOWS NEED FLORIDA | | | PRODUCT APPROVAL COVER PAGE. | | | D) ROOF TILE NEEDS MATCHING FLORIDA | | | PRODUCT APPROVAL. | | | E) WINDOW MULLIONS FOR FIXED WINDOWS: | | | CLEARLY SPECIFY SIZE OF MULLION AND | | | ANCHOR TO BE USED AT GREAT ROOM FIXED | | | WINDOW TO MEET THE DESIGN PRESSURES | | | CALCULATED ON PLANS. SEC. 104.2.1.2 CITY | | | AMENDMENTS TO FBC 2001. | | | 6- PROVIDE CLEAR WINDOW & DOOR SCHEDULES | | | WITH SIZES MATCHING PLANS. SYMBOLS TO | | | MATCH ALSO. |
|