| Plan Review Notes For Permit 05060459 |
| Permit Number |
05060459 |
|
| Review Stop |
B |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2005-12-06 00:00:00 | BUILDING REVIEW CHECKLIST: | | | 1- ENERGY CALCULATIONS SUBMITTED ARE | | | USING FBC 2004 FORM. NEED ENERGY | | | CALCULATIONS USING FBC 2001 FORM SINCE | | | THAT WAS THE CODE PLANS WERE REVIEWED | | | FOR. | | | | | | 2- APPLY FOR SHUTTERS UNDER A SEPARATE | | | PERMIT AS AGREED ON PROVISO. APPLY EARLY | | | TO AVOID DELAYS OR CONFLICTS GIVEN THE | | | LARGE VOLUME OF PERMIT APPLICATIONS THE | | | CITY IS RECEIVING. | | | | | | 3- PROVIDE PRODUCT APPROVAL FOR ATRIUM | | | DOOR THAT MATCHES SPECIFICATIONS ON | | | PLANS. SEE PLANS FOR SIZE AND SWING OF | | | DOOR. | | | | | | 4- OWES $70.00 FOR REVISION FEES. | | | | | | JULIO GOMEZ | | | BUILDING PLANS EXAMINER | | | (561)805-6712 |
|