| Plan Review Notes For Permit 05060442 |
| Permit Number |
05060442 |
|
| Review Stop |
G |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-06-22 00:00:00 | DENIED | | | REFERENCE: FBC-2001 FUEL GAS | | | | | | 1. NO PERMIT PERTAINING TO A GENERATOR | | | SHALL BE ISSUED UNTIL AN APPLICATION FOR | | | THE GENERATOR, (RES-GEN OR COM-GEN), HAS | | | BEEN APPLIED FOR. REVIEWS FOR THE | | | GENERATOR BY BUILDING, (SLAB & | | | ANCHORING), ELECTRICAL, (LISTING FOR | | | GENERATOR AND APPROVAL OF THE TRANSFER | | | SWITCH), MECHANICAL, (DISTANCE FROM | | | OPENINGS IN THE HOUSE AND HOUSES ON | | | ADJOINING PROPERTIES), AND ZONING, (TWO | | | COPIES OF A SURVEY SHOWING LOCATION OF | | | THE GENERATOR, DISTANCE FROM PROPERTY | | | LINES AND OPENINGS IN HOUSE). TWO COPIES | | | OF PLANS, SURVEYS AND SPECIFICATIONS ARE | | | REQUIRED. - THE GEN-RES WILL BE THE | | | ELECTRICAL PERMIT FOR THE GENERATOR. - | | | SEE ATTACHED SHEET FOR ADDITIONAL | | | INFORMATION REQUIRED. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|