Plan Review Notes
Plan Review Notes For Permit 05060430
Permit Number 05060430
Review Stop E
Sequence Number 1
Notes
Date Text
2005-06-23 00:00:00************** UNSAT ******************
  
 1)NOTE: PLEASE SEE MISSING TITLE BLOCK
 AND TITLE BLOCK INFORMATION AS REQUIRED
 UNDER FAC 61G15-23.002, FS 471.023.
 PLEASE SEE THIS IS REQUIRED FOR ALL
 SHEETS AND FOR ALL TRADES WHEATHER OR
 NOT COMMENT IS MADE BY OTHER
 REVIEWER(S).
  
 2)NOTE: PLEASE COMPLETE ELECTRICAL
 PLANS. PLEASE SEE NO SEC'S, FEEDER SIZES
 ARE INDICATED. THERE APPEARS TO BE
 NOTS/NUMBERS TO EACH, HOWEVER THERE IS
 NO FEEDER SCHEDULE TO CORRELATE.
 215.5,310.16,240.4 ETC
  
 3)NOTE: PLEASE SHOW ALL CIRCUITING ON
 PLANS AND CORRELATE WITH A PANEL
 SCHEDULE TO BE SUBMITTED.NO PANEL
 SCHEDULE SUBMITTED.
 215.5
  
 4)NOTE: PLEASE SUBMIT MANUFACTURE
 SPECS/CUT SHEETS FOR GENERATOR AND ATS
 SWITCH. THESE ARE TO SHOW ALL LISTINGS
 PER A NRTL.
 PLEASE ALSO SEE MECH/FIRE REVIEW
 COMMENTS, AS SPECS ETC MAY BE REQUIRED
 ALSO FOR FUEL TANK.
  
 5)NOTE: PLEASE SEE PERMIT APPLICATION
 WAS SUBMITTED FOR $1.7 MIL SCOPE OF WORK
 AND NOW INDICATES $250K?? PLEASE SUBMIT
 ONLY PLANS FOR SCOPE OF WORK PROPOSED.
 IF WORL IN THIS SCOPE IS FOR BLDG ONLY,
 THNE PLAN REVISE PERMIT APPLICATION AND
 SUBMIT PLANS FOR BLDG ONLY.
 215.5
  
 6)NOTE: PLEASE SEE 250.50 FOR MIN
 REQUIRED GROUNDING ELECTRODE SYSTEM.
 NO DETAIL PROVIDED.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]