| Date |
Text |
| 2005-07-19 00:00:00 | BUILDING PLAN REVIEW |
| | PERMIT: 05060430 |
| | ADD: 7500 NORTHLAKES BLVD |
| | CONT: METRO EQUIPMENT SERVICES |
| | TEL: (305)586-8925 |
| | |
| | FL BLD CODE= 2001 FLORIDA BUILDING CODE |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | 1ST REVIEW |
| | ACTION: DENIED |
| | |
| | 1) METRO EQUIPMENT SERVICES TO PROVIDE |
| | STATE LICENSE NUMBER FL S S 489. |
| | |
| | 2) PLANS INDICATE A PRE-MANUFACTURED |
| | CONTROL BUILDING, PROVIDE STATE |
| | APPROVED PLANS BY THE DEPARTMENT OF |
| | COMMUNITY AFFAIRS.FL S S 553.1 RULE B-1. |
| | |
| | 3) DEPENDING ON THE STATE APPROVAL FOR |
| | THE MANUFACTURED BUILDING, PRODUCT |
| | APPROVALS MAY BE REQUIRED FOR THE DOORS |
| | AND VENTS. |
| | |
| | 4) STATE APPROVED PLANS SHALL INDICATE: |
| | FL. BLD CODE 1606.1.7 THE FOLLOWING |
| | INFORMATION RELATED TO WIND SHALL BE |
| | SHOWN ON THE CONSTRUCTION DRAWINGS, |
| | 1)- BASIC WIND SPEED, MPH |
| | 2)- WIND IMPORTANCE FACTOR, & BUILDING |
| | CATEGORY |
| | 3)- WIND EXPOSURE |
| | 4)- INTERNAL PRESSURE COEFFICIENT, |
| | 5)- COMPONENTS & CLADDING, THE DESIGN |
| | WIND PRESSURES IN TERMS OF PSF. |
| | |
| | 5) THIS STRUCTURE IS IN A "A" FLOOD ZONE |
| | |
| | THE FLOOD HEIGHT HAS NOT BEEN |
| | DETERMINED, HAS THE BASE FLOOD HEIGHT |
| | FOR THE CONTROL BUILDING BEEN |
| | CONSIDERED? |
| | BUILDING PLAN REVIEW |
| | JIM WITMER |
| | TEL: (561)805-6715 |
| | FAX: (561)659-8026 |
| | |
| | |
| | |