| Plan Review Notes For Permit 05060379 |
| Permit Number |
05060379 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-06-14 00:00:00 | | | | PLEASE SUBMIT DETAILS FOR THE PANEL | | | SHOWN ON THE SCHEMATIC, FEEDER AND | | | CONDUIT SIZE AND TYPE, PANEL RATING AND | | | OCP, PANEL SCHEDULE AND COMPUTED LOAD, | | | ETC. IF AN ELECTRIC HEATER IS TO BE | | | INSTALLEDPLEASE SUBMIT CALCULATIONS | | | FOR THE MAINSERVICE. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 | | | |
|