| Plan Review Notes For Permit 05060375 |
| Permit Number |
05060375 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2005-07-25 00:00:00 | ******** UNSAT ********* | | | | | | 1)NOTE: PLEASE SEE PREVIOUS REVIEW WHICH | | | REFERENCED TO FS 481.221 WHICH REQUIRES | | | THE ORIGINAL SIGNATURE FOR ARCHITECT OF | | | RECORD. | | | PLEASE SEE PLANS WHICH FIRST CAME IN | | | WERE SEALED PHOTOCOPIES OF SIGNED PLANS. | | | PLEASE NOW SEE NEW PLANS SUBMITTED ARE | | | ALSO SEALED PHOTCOPIES OF SIGNED PLANS | | | WITH A PEN TRACED OVER ARCHITECT'S | | | SIGNATURE. THIS IN NOT ACCEPTABLE TO | | | THIS OFFICE PER FS 481.221. | | | ONE COPY OF EACH SHALL BE REAINED FOR | | | FILE AND POSSIBLE REVIEW BY THE STATE | | | BOARD OF ARCH'S, AND DBPR. | | | | | | 2)NOTE: PLEASE SEE LOADS NOW SHOWN FOR | | | NEW RECEPTS DO NOT CORRELATE WITH PLANS. | | | PLEASE SEE 220.13 FOR A MIN OF 180V PER | | | OUTLET. | | | PLEASE ADJUST. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW. | | | 561-805-6717 | | | [email protected] |
|