Plan Review Notes
Plan Review Notes For Permit 05060375
Permit Number 05060375
Review Stop E
Sequence Number 2
Notes
Date Text
2005-07-25 00:00:00******** UNSAT *********
  
 1)NOTE: PLEASE SEE PREVIOUS REVIEW WHICH
 REFERENCED TO FS 481.221 WHICH REQUIRES
 THE ORIGINAL SIGNATURE FOR ARCHITECT OF
 RECORD.
 PLEASE SEE PLANS WHICH FIRST CAME IN
 WERE SEALED PHOTOCOPIES OF SIGNED PLANS.
 PLEASE NOW SEE NEW PLANS SUBMITTED ARE
 ALSO SEALED PHOTCOPIES OF SIGNED PLANS
 WITH A PEN TRACED OVER ARCHITECT'S
 SIGNATURE. THIS IN NOT ACCEPTABLE TO
 THIS OFFICE PER FS 481.221.
 ONE COPY OF EACH SHALL BE REAINED FOR
 FILE AND POSSIBLE REVIEW BY THE STATE
 BOARD OF ARCH'S, AND DBPR.
  
 2)NOTE: PLEASE SEE LOADS NOW SHOWN FOR
 NEW RECEPTS DO NOT CORRELATE WITH PLANS.
 PLEASE SEE 220.13 FOR A MIN OF 180V PER
 OUTLET.
 PLEASE ADJUST.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW.
 561-805-6717
 [email protected]