| 2005-06-26 00:00:00 | BUILDING PLAN REVIEW |
| | PERMIT: 05060127 |
| | ADD: 500 S AUSTRALIAN AV # 825 |
| | CONT: KARL CORP |
| | TEL: (561)718-3799 |
| | FL BLD CODE= 2001 FLORIDA BUILDING CODE |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | 1ST REVIEW |
| | ACTION: DENIED |
| | |
| | 1) 704.2.1.4 CORRIDOR PARTITIONS, SMOKE |
| | STOP PARTITIONS, HORIZONTAL EXIT PART- |
| | ITIONS, EXIT ENCLOSURES, AND FIRE |
| | RATED WALLS REQUIRED TO HAVE PROTECTED |
| | OPENINGS SHALL BE EFFECTIVELY AND |
| | PERMANETLY IDENTIFIED WITH SIGNS OR |
| | STENCILING IN A MANNER ACCEPTABLE TO THE |
| | AUTHORITY HAVING JURISDICTION. SUCH IDEN |
| | TIFICATION SHALL BE ABOVE ANY DECORATIVE |
| | CEILING CEILING AND IN CONCEALED SPACES. |
| | SUGGESTED WORDING" FIRE & SMOKE BARRIER |
| | PROTECT ALL OPENINGS". |
| | |
| | 2) SHEET A2.1 REFLECTED CEILING PLAN |
| | MISSING EXIT DIRECTIONAL SIGNAL LIGHTS |
| | 1016.3.1 EXITS SHALL BE MARKED BY AN |
| | APPROVED SIGN READILY VISIBLE FROM |
| | ANY DIRECTION OF EXIT ACCESS.EVERY |
| | EXIT SIGN SHALL BE SUITABLY |
| | ILLUMINATED BY A RELIABLE LIGHT |
| | SOURCE.EXTERNALLY AND INTERNALLY |
| | ILLUMINATED SIGNS SHALL BE VISIBLE IN |
| | BOTH THE NORMAL AND EMERGENCY |
| | LIGHTING. |
| | |
| | 3) TI-1 DOOR DETAIL- BUCKS TO BE: |
| | 609.2.1 TYPE I AND TYPE II |
| | CONSTRUCTION. PARTITIONS SHALL BE |
| | CONSTRUCTED OF NONCOMBUSTIBLE MATERIALS. |
| | BUILDING PLAN REVIEW |
| | JIM WITMER |
| | TEL: (561)805-6715 |
| | FAX: (561)659-8026 |