2005-06-26 00:00:00BUILDING PLAN REVIEW
 PERMIT: 05060127
 ADD: 500 S AUSTRALIAN AV # 825
 CONT: KARL CORP
 TEL: (561)718-3799
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 1) 704.2.1.4 CORRIDOR PARTITIONS, SMOKE
 STOP PARTITIONS, HORIZONTAL EXIT PART-
 ITIONS, EXIT ENCLOSURES, AND FIRE
 RATED WALLS REQUIRED TO HAVE PROTECTED
 OPENINGS SHALL BE EFFECTIVELY AND
 PERMANETLY IDENTIFIED WITH SIGNS OR
 STENCILING IN A MANNER ACCEPTABLE TO THE
 AUTHORITY HAVING JURISDICTION. SUCH IDEN
 TIFICATION SHALL BE ABOVE ANY DECORATIVE
 CEILING CEILING AND IN CONCEALED SPACES.
 SUGGESTED WORDING" FIRE & SMOKE BARRIER
 PROTECT ALL OPENINGS".
  
 2) SHEET A2.1 REFLECTED CEILING PLAN
 MISSING EXIT DIRECTIONAL SIGNAL LIGHTS
 1016.3.1 EXITS SHALL BE MARKED BY AN
 APPROVED SIGN READILY VISIBLE FROM
 ANY DIRECTION OF EXIT ACCESS.EVERY
 EXIT SIGN SHALL BE SUITABLY
 ILLUMINATED BY A RELIABLE LIGHT
 SOURCE.EXTERNALLY AND INTERNALLY
 ILLUMINATED SIGNS SHALL BE VISIBLE IN
 BOTH THE NORMAL AND EMERGENCY
 LIGHTING.
  
 3) TI-1 DOOR DETAIL- BUCKS TO BE:
 609.2.1 TYPE I AND TYPE II
 CONSTRUCTION. PARTITIONS SHALL BE
 CONSTRUCTED OF NONCOMBUSTIBLE MATERIALS.
 BUILDING PLAN REVIEW