| Plan Review Notes For Permit 05060125 |
| Permit Number |
05060125 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2005-06-30 00:00:00 | BUILDING PLAN REVIEW: PROVISO | | | | | | 1. SUBMIT A COMPLETED INSTALLATION | | | SCHEDULE.THE ONE SUBMITTED ONLY SHOWED | | | OPENING WIDTH & HEIGHT & NUMBER OF | | | PANELS & HEIGHT OF PANELS. NEED TO KNOW | | | ANCHORING DETAIL ( O.C. SPACING ) & TYPE | | | OF FASTENER. (SEE PAGES 3 & 4) | | | | | | 2. SEE PAGE 5 OF DRAWING 03-235 & SUBMIT | | | THE INFORMATION ON TABLE 3 & 4. | | | | | | | | | ANY QUESTIONS PLEASE CALL: | | | LEA SMITH, BUILDING PLANS EXAMINER | | | 805-6713 | | | E-MAIL: [email protected] |
|