Plan Review Notes
Plan Review Notes For Permit 05060104
Permit Number 05060104
Review Stop M
Sequence Number 2
Notes
Date Text
2005-08-23 00:00:00MECH. NOTES:
  
 GENERATOR MANF. RECOMBINATIONS FOR
 SERVISE CLEARANCE/VENILATION IN
 FEET/INCHES IN ALL DIRECTION MUST ACCOM.
 GENERATOR PERMIT APP.
  
 GENERATOR EXHAUST MUST BE TEN FEET
 AWAY FROM ANY BUILDING OPENING, AND
 EXHAUST MUST BE DIRECTED AWAY FROM
 BUILDING.AND BE TEN FEET FROM PROPITY
 LINE. 2001 FBC/M 804.3.3.TERMINATION.
 2001 FBC/M SECTION 915
 REQUIRMENT OF NFPA 37 8.2.3.2
 EXHAUST SYSTEM TERMINATION
  
 INFORMATION ON TYPE OF FUEL.
  
 LP/NAT GASS REQUIRE PERMIT, FROM
 LICENSED GAS CONTRACTOR.
  
 PAT RAFTER 561/805/6728 OR 805/6719
 PATTY KRAUSS.
  
  
  
  