| Plan Review Notes For Permit 05060090 |
| Permit Number |
05060090 |
|
| Review Stop |
E |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2005-08-31 00:00:00 | ****** PROVISO/ REVISION ******** | | | | | | | | | 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR | | | ALL NEW SERVICE EQUIPMENT BEING INSTALL- | | | ED. MAINS/BRKRS AND PANELS ARE ALL TO BE | | | RATED FOR THE AVAILABLE FAULT CURRENT. | | | PER 110.9/215.5 | | | AIC RATING SHOWN FOR PANEL, HOWEVER NOT | | | INDICATED FOR MAIN DISCONNECT. | | | | | | 2)NOTE: PLEASE SEE MISSING EQUIPMENT | | | GROUNDING CONDUCTOR FROM MAIN TO PANEL. | | | 250.110,250.24 AND SIZED PER 250.122 | | | | | | 3)NOTE: PLEASE SEE FAN J-BOX IN BEDRMS | | | DOES NOT MEET THE REQUIREMENTS OF 210.70 | | | AND NFPA-101 5-8 | | | PLEASE SEE AN OUTLET/LT FIXTURES SHALL | | | BE PROVIDED. | | | | | | 4)NOTE: PLEASE SEE MIN CLEARENCE | | | REQUIRED FOR DISCONNECT FOR AHU. | | | 110.26 | | | | | | 5)NOTE: PLEASE SEE MISSING GFI RECEPT | | | REQUIRED IN BATHRM. | | | 210.52D,210.8, 210.11C3 | | | MUST BE 20A AND #12 AWG. | | | | | | 6)NOTE: PLEASE PROVIDE ROOM/AREA | | | DESIGNATIONS ON PLANS. | | | | | | PLEASE SUBMIT THE ABOVE REVISED PLANS | | | BEFORE ANY ELECTRICAL INSPECTIONS ARE | | | CALLED IN. | | | THIS INCLUDES ROUGH UNDERGROUND/STEEL | | | FOOTING INSPECTION. | | | | | | IF THERE ARE ANY QUESTIONS, PLEASE CALL. | | | | | | DEWEY PALMER. | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] | | | ********** NOTE ************* | | | | | | IF PLANS ARE RETURNED FOR ANY OTHER | | | COMMENTS FROM OTHER TRADES, PLEASE | | | ADDRESS "PROVISO" AT THIS TIME. |
|