Plan Review Notes
Plan Review Notes For Permit 05060090
Permit Number 05060090
Review Stop E
Sequence Number 3
Notes
Date Text
2005-08-31 00:00:00****** PROVISO/ REVISION ********
  
  
 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT BEING INSTALL-
 ED. MAINS/BRKRS AND PANELS ARE ALL TO BE
 RATED FOR THE AVAILABLE FAULT CURRENT.
 PER 110.9/215.5
 AIC RATING SHOWN FOR PANEL, HOWEVER NOT
 INDICATED FOR MAIN DISCONNECT.
  
 2)NOTE: PLEASE SEE MISSING EQUIPMENT
 GROUNDING CONDUCTOR FROM MAIN TO PANEL.
 250.110,250.24 AND SIZED PER 250.122
  
 3)NOTE: PLEASE SEE FAN J-BOX IN BEDRMS
 DOES NOT MEET THE REQUIREMENTS OF 210.70
 AND NFPA-101 5-8
 PLEASE SEE AN OUTLET/LT FIXTURES SHALL
 BE PROVIDED.
  
 4)NOTE: PLEASE SEE MIN CLEARENCE
 REQUIRED FOR DISCONNECT FOR AHU.
 110.26
  
 5)NOTE: PLEASE SEE MISSING GFI RECEPT
 REQUIRED IN BATHRM.
 210.52D,210.8, 210.11C3
 MUST BE 20A AND #12 AWG.
  
 6)NOTE: PLEASE PROVIDE ROOM/AREA
 DESIGNATIONS ON PLANS.
  
 PLEASE SUBMIT THE ABOVE REVISED PLANS
 BEFORE ANY ELECTRICAL INSPECTIONS ARE
 CALLED IN.
 THIS INCLUDES ROUGH UNDERGROUND/STEEL
 FOOTING INSPECTION.
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER.
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
 ********** NOTE *************
  
 IF PLANS ARE RETURNED FOR ANY OTHER
 COMMENTS FROM OTHER TRADES, PLEASE
 ADDRESS "PROVISO" AT THIS TIME.