| 2005-06-27 00:00:00 | DENIED |
| | 1)A RECORDED COPY OF THE NOTICE OF |
| | COMMENCEMENT MUST BE SUBMITTED BEFORE A |
| | PERMIT CAN BE ISSUED. |
| | |
| | 2)IMPACT FEES MUST BE PAID TO PALM |
| | BEACH COUNTY, PLANS STAMPED BY THEM AND |
| | COPY OF RECEIPT SUBMITTED TO CITY OF |
| | WEST PALM BEACH BUILDING DEPARTMENT, |
| | BEFORE A BUILDING PERMIT CAN BE ISSUED. |
| | |
| | 3) THE RIGHT SIDE ELEVATION ON A2 DOES |
| | NOT INDICATE THE THREE WINDOWS THAT ARE |
| | SPECIFIED ON THE FLOOR PLAN. |
| | |
| | 4) REVISE THE WALL SECTION ON A3 TO |
| | COMPLY WITH FBC 1804.1.3 AND CITY |
| | AMENDMENT 1804.1.7, WHICH REQUIRE THE |
| | BOTTOM OF THE FOOTING TO BE A MINIMUM OF |
| | 12 INCHES BELOW GRADE AND THE FLOOR |
| | ELEVATION TO BE A MINIMUM OF 4 INCHES |
| | ABOVE GRADE. |
| | |
| | 5) PROVIDE STRUCTURAL DETAILS FOR THE |
| | COLUMNS AT THE FRONT PORCH. |
| | |
| | 6) SPECIFY THE LINTEL SIZE AND |
| | REINFORCEMENT IN THE LINTEL SCHEDULE ON |
| | A4. |
| | |
| | 7) REVISE ROOF SHEATHING FASTENING NOTES |
| | ON D1. CITY AMENDMENT TO FBC TABLE |
| | 2306.1, REQUIRES 8D COMMON NAILS AT |
| | 4"O.C. AT EDGES AND 6"O.C. INTERMEDIATE |
| | IN ZONE 3. ZONE 3 INCLUDES THE OUTSIDE |
| | CORNERS OF HIP ROOFS IN ADDITION TO |
| | GABLE ENDS. |
| | |
| | 8) SPECIFY ON THE FLOOR PLAN THAT THE |
| | WALL BETWEEN THE GARAGE AND THE LIVING |
| | SPACE IS INSULATED AS INDICATED ON THE |
| | ENERGY CALC. FORM. |
| | |
| | 9) THE TYPICAL WALL SECTION ON A3 SHOWS |
| | AN 8X8 BOND BEAM WITH ONE #5 REBAR AND |
| | D1 HAS A 8X16 BOND BEAM WITH TWO #5 |
| | REBARS. PLEASE CLARIFY. |
| | |
| | 10) PRODUCT APPROVALS SUBMITTED WITH |
| | PERMIT APPLICATION AFTER OCTOBER 1, 2003 |
| | ARE REQUIRED TO COMPLY WITH THE FLORIDA |
| | PRODUCT APPROVAL SYSTEM. FOR INFORMATION |
| | PLEASE SEE THE STATE WEBSITE AT |
| | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH |
| | STATEWIDE APPROVAL ARE REQUIRED TO BE |
| | SUBMITTED WITH A COVER SHEET THAT LISTS |
| | THE PRODUCT IDENTITY NUMBER FROM THE |
| | STATE. IF THE PRODUCT DOES NOT HAVE |
| | STATEWIDE APPROVAL, SUBMIT AN APPLICA- |
| | TION FOR LOCAL PRODUCT APPROVAL OR SITE |
| | SPECIFIC FORM PER RULE 9B-72. SUBMIT |
| | COVER SHEETS WITH THE APPROPRIATE FL # |
| | FOR THE PRODUCT AND THE TESTING AND |
| | INSTALLATION DRAWINGS THAT WERE |
| | SUBMITTED AND APPROVED BY THE STATE. |
| | |
| | 11) SUBMIT PRODUCT APPROVAL FOR THE |
| | FOLLOWING: STRUCTURAL WINDOW MULLIONS, |
| | SLIDING GLASS DOOR AND OUTSWING FRONT |
| | DOOR. |
| | |
| | 12) SUBMIT (2) COPIES OF A KEY PLAN AND |
| | AN INSTALLATION SCHEDULE FOR THE STORM |
| | PANELS. SPECIFY THE TYPE OF MOUNT, THE |
| | FASTENER TYPE AND FASTENER SPACING. |
| | |
| | THE CALCULATED VALUE FOR THE STRUCTURE |
| | HAS BEEN INCREASED BASED ON SBCCI/ICC |
| | BUILDING VALUATION DATA. THE NEW VALUE |
| | IS $142,796. ADDITIONAL PERMIT FEES ARE |
| | DUE. |
| | |
| | ROBERT MCDOUGAL |
| | BLDG. PLAN REVIEW |
| | (561)805-6714 |
| | |