| 2005-08-03 00:00:00 | IN ELECTRIC FOR REVIEW. |
| | CALLED CONTRACTOR TO GO OVER ELECTRICAL |
| | PLANS SUBMITTED. NO SPECS FOR ATS , ETC |
| | SUBMITTED. |
| | ENGINEER TO BE CALLED BY CONTRACTOR TO |
| | GO OVER ELECTRICAL. |
| | ****** UNSAT 2ND REVIEW ****** |
| | |
| | PLEASE SEE SOME NOTES FROM PREVIOUS |
| | REVIEW STILL NEED TO BE ADDRESSED. |
| | |
| | THESE ARE TAKEN DIRECTLY FROM PREVIOUS |
| | REVIEW AND RESPONSE LTR SUBMITTED. |
| | |
| | 1)NOTE: NOTE #1, OK. |
| | |
| | 2)NOTE: NOTE #2, OK, EXCEPTION FOR OCP |
| | AT GEN OK. |
| | |
| | 3)NOTE: NOTE #3, NO, PLEASE SEE SPEC |
| | BOOKS WERE SUBMITTED SHOWING A DIFFERENT |
| | RATING. |
| | PLEASE NOW, SEE ALL SPECS FOR GENERATOR, |
| | SUB-BASE FUEL TANK, ATS ETC WERE NOT |
| | SUBMITTED BACK WITH PLANS AND PERMIT |
| | APPLICATION. THIS IS REQUIRED FOR |
| | REVIEW. |
| | |
| | 4)NOTE: NOTE #4 NO,PLEASE SEE |
| | 225.31,-225.36 AS NOTED ON PREVIOUS |
| | REVIEW.THE DISCONNECTING MEANS ON |
| | GENERATOR IS NOT AN ACCEPTABLE MEANS OF |
| | DISCONNECT REQUIRED. |
| | |
| | 5)NOTE: NOTE #5 NO. PREVIOUS NOTES. |
| | 225.36 |
| | |
| | 6)NOTE: NOTE #6, OK, CORRECTED. |
| | |
| | 7)NOTE: NOTE #7 NO. PLEASE SEE RESPONSE |
| | LTR MENTIONS "NO SPECS SUBIMTTED" , |
| | HOWEVER PLEASE CONTACT ELECTRICAL |
| | CONTRACTOR AS REQUIRED SPECS WERE INDEED |
| | SUBMITTTED FOR REVIEW ON ORIGINAL |
| | SUBMITTED PACKAGE. |
| | GROUND FOR FOOTER STEEL ADDED, OK. |
| | NOTE FOR GENERATOR BEING A "SEPARATELY |
| | DERIVED SYSTEM" SHOULD BE ADDED TO |
| | RISER. IT IS KNOWN THAT THE ATSSHOWN |
| | ON PLANS IS A 4-POLE ATS FOR SEPARATELY |
| | DERIVED SYSTEMAND ALSO NOTED THATTHE |
| | NEUTRAL TO GROUNDWAS SHOWN TO NEW |
| | GROUNDING ELECTRODE SYSTEM. PLEASE SEE |
| | SPECS SUBMITTED, (NOT PART OF ENGINEER'S |
| | PLANS) INDICATED A 3-POLE ATS AND WAS |
| | THE REASON FOR COMMENT. |
| | |
| | NEW NOTE: |
| | |
| | 8)NOTE: PLEASE SEE ONLY ONE COPY OF |
| | ORIGINALASP-1/A_1 SHEETS/SETS WERE |
| | SUBMITTED. IT IS NOTED THAT NEW A-1 |
| | SHEETS WERE SUBMITTED, HOWEVER 2ND COPY |
| | OF ASP-1 WAS NOT SUBMITTED BACK WITH |
| | SET. |
| | |
| | ************************************* |
| | PLEASE REMOVE ANY OLD/VOIDED SHEETS AND |
| | ONLY INSERT NEW REVISED SHEETS INTO |
| | COMPLETE SETS FOR REVIEW AND STAMPING. |
| | PLEASE SUBMIT TWO COMPLETE SETS FOR |
| | REVIEW AND STMAPING. |
| | ONCE AGAIN, IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE IN CONTACTING |
| | THIS OFFICE. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-805-6717 |
| | [email protected] |